Group Rating Required for External Signs
Under NCC clause C2D14, the Group rating depends on the building’s Class and its rise in storeys.
| Rise in storeys |
Class 2, 3, 9 Apartments, hotels, hospitals, schools, aged care |
Class 5, 6, 7, 8 Offices, shops, factories, warehouses, car parks |
| 1 | None | None |
| 2 | Group 1 or 2* | None |
| 3 | Group 1 or 2 | Group 1 or 2 |
| 4 or more | Group 1 or 2 | Group 1 or 2 |
| Freestanding pylon or monolith Not fixed to a building | None |
Where Group 1 or 2 applies, NCC clause C2D14(h) permits the sign only if it:
- “achieves a group number of 1 or 2”
The sign must have a Group 1 or Group 2 result, as shown in the table above.
- “does not extend beyond one storey”
The sign must fit within the height of a single storey of the building. It can’t cross from one storey into another.
- “does not extend beyond one fire compartment”
A fire compartment is a part of the building separated by fire-resisting walls or floors. The sign can’t cross from one compartment into another.
- “is separated vertically from other signs permitted under (h) by at least 2 storeys”
Any other sign that relies on this same rule must be at least 2 storeys above or below this sign.
* A 2-storey Class 2, 3 or 9c building may be Type C under C2D6, in which case no rating applies. For mixed-use buildings, C2D4 uses the Class of the top storey.
Source: NCC 2022 Volume One (Amdt 2), Table C2D2 and clauses C2D3, C2D4, C2D6, C2D10 and C2D14. Same wording in NCC 2025, adopted in SA from 1 May 2027.